Automatic Positioning Fire Monitor
Intelligent Series · Flame detection · Auto-targeting · Detection-linked suppression · Water & foam
Automatic Positioning Fire Monitor
The CA-FIRE automatic positioning fire monitor is a complete automatic tracking & positioning jet fire-extinguishing system. Using infrared and ultraviolet sensors, it detects the radiation released by a fire, scans the protected 3D space, drives the nozzle precisely onto the fire source, then automatically opens the valve, starts the pump and discharges — extinguishing a fire in its earliest stage with no human input.
The system combines the monitor, a field control box, a central control cabinet and an Ethernet AI management platform with HD camera — delivering long detection range, large coverage area, high sensitivity, fast response and full-area monitoring with no blind spots.
How Automatic Positioning Works
Product Video — Automatic Positioning in Action
Key Features
System Components
System Architecture
System architecture: each monitor links through a junction box to the field control box (ZDMAN-NX), which connects to the central control cabinet (ZDM-ZK01) in the fire control room over a single optical fibre. Field control box outputs the fire-alarm interlock and pump-control signals. CAN H/L terminals must correspond — do not reverse.
Installation & Wiring Diagram
WDZN-RYSP 2×1.0mm² — CAN communication lineWDZN-RVV 3×1.0mm² — Power line (box ↔ monitor)WDZN-RVV 2×1.0mm² — Fire alarm interlock (volt-free NO)WDZN-RVV 4×1.0mm² — Pump control & feedbackWDZN-RVV 3×2.5mm² — 220VAC device power (mains in)ZDMS Automatic Fire Monitor Models
The CA-FIRE ZDMS series automatic positioning fire monitors are available in four configurations — standard water, foam-water, explosion-proof water and explosion-proof foam-water — with flow rates from 5 to 50 L/s, jet radius up to 73 m and 360° horizontal coverage.
| Model | ZDMS0.6/5S | ZDMS0.6/10S | ZDMS0.8/20S | ZDMS0.8/30S | ZDMS0.8/40S | ZDMS0.8/50S |
|---|---|---|---|---|---|---|
| Flow Rate ±8% (L/s) | 5 | 10 | 20 | 30 | 40 | 50 |
| Working Pressure (MPa) | 0.6 | 0.6 | 0.8 | 0.8 | 0.8 | 0.8 |
| Jet Radius (m) | 34 | 39 | 56 | 62 | 67 | 73 |
| Max Protection Radius (m) | 30 | 35 | 50 | 55 | 60 | 65 |
| Monitoring Radius (m) | 40 | 40 | 65 | 65 | 70 | 70 |
| Installation Height (m) | 6–20 | 6–25 | 8–35 | 8–35 | 8–35 | 8–35 |
Positioning time ≤30 s (5/10S) / ≤60 s · Working voltage DC12–24V · Horizontal swing 360° · Vertical −90° to +30° · Working temp −10 to +50°C · Flange G1¼" or DN80/DN100 GB/T9119-2000.
| Model | ZDMS0.8/30P | ZDMS0.8/40P | ZDMS0.8/50P |
|---|---|---|---|
| Flow Rate ±8% (L/s) | 30 | 40 | 50 |
| Working Pressure (MPa) | 0.8 | 0.8 | 0.8 |
| Jet Radius (m) | 50 | 56 | 62 |
| Max Protection Radius (m) | 45 | 50 | 55 |
| Monitoring Radius (m) | 65 | 70 | 70 |
| Foaming Ratio (20°C) | ≥6 | ≥6 | ≥6 |
| Mixture Ratio | 6–7% | 6–7% | 6–7% |
25% drainage time ≥150 s · Positioning ≤60 s · 24VDC · Installation height 8–35 m · 360° swing · −90° to +30° · −10 to +55°C · DN80/DN100 flange · Turning radius 700 mm.
| Model | ZDMS0.8/20S-Ex | ZDMS0.8/30S-Ex | ZDMS0.8/40S-Ex | ZDMS0.8/50S-Ex |
|---|---|---|---|---|
| Flow Rate ±8% (L/s) | 20 | 30 | 40 | 50 |
| Working Pressure (MPa) | 0.8 | 0.8 | 0.8 | 0.8 |
| Jet Radius (m) | 56 | 62 | 67 | 73 |
| Max Protection Radius (m) | 50 | 55 | 60 | 65 |
| Monitoring Radius (m) | 65 | 65 | 70 | 70 |
Explosion-proof class: Ex d IIB T4 Gb IP65–67 / Ex d IIC T4 Gb IP65–67 · Positioning ≤60 s · DC24V · Installation height 8–35 m · 360° swing · −90° to +30° · −10 to +55°C · DN80/DN100 flange · Turning radius 600 mm.
| Model | ZDMS0.8/30P-Ex | ZDMS0.8/40P-Ex | ZDMS0.8/50P-Ex |
|---|---|---|---|
| Flow Rate ±8% (L/s) | 30 | 40 | 50 |
| Working Pressure (MPa) | 0.8 | 0.8 | 0.8 |
| Jet Radius (m) | 50 | 56 | 62 |
| Max Protection Radius (m) | 45 | 50 | 55 |
| Monitoring Radius (m) | 65 | 70 | 70 |
| Foaming Ratio (20°C) | ≥6 | ≥6 | ≥6 |
| Mixture Ratio | 6–7% | 6–7% | 6–7% |
Explosion-proof class: Ex d IIB T4 Gb IP65–67 / Ex d IIC T4 Gb IP65–67 · 25% drainage time ≥150 s · Positioning ≤60 s · DC24V · 8–35 m · 360° swing · −90° to +30° · −10 to +55°C · DN80/DN100 flange · Turning radius 800 mm.
Control System Parameters
| Field Control Box — ZDMAN-NX | |
| Working Voltage | 220VAC 50Hz |
| Communication | Field CAN bus · remote Ethernet |
| Dimensions | 250 × 180 × 80 mm |
| Mounting | Wall, 1.2–1.5 m above floor |
| Central Control Cabinet — ZDM-ZK01 | |
| Working Voltage | 220VAC 50Hz |
| Communication | Ethernet |
| Dimensions | 950 × 600 × 1280 mm |
| Installation | Floor-standing in fire control room |
The ZDMS monitor models above are matched to the ZDMAN-NX field control box and ZDM-ZK01 central cabinet. Detector count, coverage layout and mounting height are confirmed per project — contact CA-FIRE with your area dimensions and hazard class.