Model ZSDF7 / ZSXDF7 — Wafer Type · Fire Isolation Valve
Gear Operated
Butterfly Valve
Worm gear actuated wafer butterfly valve for fire sprinkler and standpipe systems. Fits between ANSI 150 / DIN PN16 / GB PN16 flanges — no adapter required. ZSXDF7 model includes DC24V supervisory tamper switch for NFPA 13 / NFPA 72 compliance. DN50–DN300, 1.6 MPa. GGG40 or SS316 body. China fire valve manufacturer, shipped worldwide.
Product Variants
Two Models — Signal & Non-Signal
Both use the same wafer body, EPDM seat, and worm gear actuator. The only difference is whether the valve includes a DC24V tamper switch for FACP supervisory wiring.
- Integrated DC24V 0.5A tamper switch
- Outputs OPEN / TAMPER / CLOSED to FACP
- NFPA 72 Chapter 17 supervisory signal compliance
- Required for electrically supervised fire main isolation per NFPA 13 Section 8.16
- Standard for commercial sprinkler risers, zone control valves, and any valve on a monitored fire alarm system
- No tamper switch — lower cost
- Physical lock-open or padlock supervision only
- Suitable for drain valves, test lines, pump test loops
- For valves where AHJ accepts non-electrical supervision
- Same body, seat, and pressure rating as ZSXDF7
Key Features
Why Specify the ZSDF7 Series
Eight design points that make the ZSDF7 / ZSXDF7 the standard gear-operated wafer butterfly valve for fire protection in commercial, industrial, and high-rise projects.
Technical Data
Full Technical Specifications
Both ZSDF7 and ZSXDF7 share the same wafer body, EPDM seat, 1.6 MPa pressure rating, and DN50–DN300 size range. The tamper switch is the only difference.
| Parameter | ZSXDF7 — With Signal | ZSDF7 — Without Signal |
|---|---|---|
| Model | ZSXDF7-Q-50-300-16 | ZSDF7-Q-50-300-16 |
| Nominal Diameter | DN50 / DN65 / DN80 / DN100 / DN125 / DN150 / DN200 / DN250 / DN300 | |
| Working Pressure | 1.6 MPa (16 bar / 232 psi) | |
| Strength Test Pressure | 6.4 MPa | |
| Seal Test Pressure | 3.2 MPa | |
| Applicable Media | Water · AFFF foam-water · AR-AFFF · Protein foam | |
| Actuator | Worm gear (涡轮蜗杆) handwheel | |
| Tamper Switch | DC24V 0.5A output (OPEN / TAMPER / CLOSED) | None |
| Switch Electrical Rating | DC24V 1.5A rated | — |
| Connection Type | Wafer — between flanges (ANSI 150 / DIN PN16 / GB PN16) | |
| Body Material | Ductile cast iron GGG40 / Stainless steel SS316 | |
| Disc Material | Ductile cast iron / Stainless steel SS316 | |
| Seat Material | EPDM | |
| Stem Material | Stainless steel | |
| Media Temperature | 0–80°C (signal version) | 4–70°C |
| Applicable Standard | GB 5135.13 | GB 5135.2 |
Structural Dimensions
Face-to-Face Length — Wafer Type
Use these face-to-face (F/F) dimensions for valve station layout, pipe spool fabrication, and interference checks. All dimensions in mm. Wafer type is 15–85 mm shorter than the equivalent grooved type per size.
| DN (mm) | 50 | 65 | 80 | 100 | 125 | 150 | 200 | 250 | 300 |
|---|---|---|---|---|---|---|---|---|---|
| F/F (mm) | 45 | 50 | 50 | 55 | 60 | 60 | 65 | 70 | 80 |
Applications
Where the ZSDF7 Is Specified
Standard gear-operated wafer butterfly valve for fire main isolation wherever flanged pipe is used. Typical project types:
Selection Guide
ZSDF7 vs. ZSXDF7 — Which to Specify
The decision comes down to one question: does the project require electrically supervised valve position monitoring?
- Project has a fire alarm control panel (FACP)
- NFPA 13 Section 8.16 electrical supervision is required
- AHJ or insurance underwriter requires monitored valve position
- Valve is on a water supply riser or zone control assembly
- System includes fire pump isolation per NFPA 20
- Valve is on a drain, test line, or pump test loop only
- AHJ accepts physical lock-open supervision (padlock + chain)
- No fire alarm system present on the project
- Cost reduction is a priority for non-supervised valve locations
- Temporary or construction phase fire protection
FAQ
Frequently Asked Questions
Common questions about the ZSDF7 / ZSXDF7 gear operated wafer butterfly valve for fire protection.
Butterfly Valve Family
Other Butterfly Valves in the CA-FIRE Range
All share the same 1.6 MPa rating, EPDM seat, and GB 5135 certification.
ZSDF7-S / ZSXDF7-S
Lever Butterfly Valve
Quarter-turn lever handle for DN50–DN150 branch lines, test-and-drain, and zone control valves. Faster operation than gear type.
ZSDF8 / ZSXDF8
Grooved Butterfly Valve
Victaulic-compatible grooved end for grooved pipe systems. 40% faster installation. Gear or lever. DN50–DN300.
ZSXDF7 / ZSXDF8 — Ex
Explosion Proof Butterfly Valve
Ex db IIC T6 Gb + Ex tb IIIC T80°C Db. IP66. For Zone 1/2 hazardous areas. Wafer & grooved. DN50–DN300.
Request a Quote or Datasheet
Ready to Specify the ZSDF7?
DN50–DN300 · GGG40 or SS316 · Signal or non-signal · Factory direct with fast lead times. Send us your pipe size, system pressure, and supervision requirement.