fire sprinkler heads

ESFR Fire Sprinkler

Home > Fire Sprinkler Heads > ESFR Fire Sprinkler
K14.2 / K17.0 / K25.2 (K202 / K242 / K363) Ceiling Heights 9.0–13.5 m Storage up to 12.0 m high Upright (U) & Pendent (P) 68°C / 74°C / 82°C / 100°C Min. Pressure 0.15–0.50 MPa Spacing 2.4–3.7 m GB 5135 CCCF Certified NFPA 13 Docs Available

Conventional sprinklers are designed to control a fire — they limit its spread and keep it from overwhelming the structure until the fire brigade arrives. An ESFR (Early Suppression Fast Response) fire sprinkler does something fundamentally different: it delivers enough water, fast enough, to suppress a high-challenge fire in high-piled storage before it reaches full involvement — often eliminating the need for costly in-rack sprinkler systems entirely.

ESFR achieves this through three simultaneous engineering advantages: a very large K-factor (K14.2 to K25.2) delivering significantly higher flow rates than standard sprinklers, a fast response glass bulb (RTI ≤50) that activates early in fire development, and a deep-penetrating spray pattern specifically shaped to drive water through the turbulent thermal column above a rack-storage fire and reach the burning commodity at shelf level.

CA-FIRE manufactures three ESFR K-factor series — ESFR-202 (K14.2), ESFR-242 (K17.0), and ESFR-363 (K25.2) — in upright (U) and pendent (P) orientations, covering ceiling heights from 9.0 m to 13.5 m and storage heights up to 12.0 m. All models are GB 5135 CCCF type approved; NFPA 13 documentation available for international submittals.

K14.2–K25.2K-factor range (intl.)
13.5 mMax ceiling height
12.0 mMax storage height
RTI ≤50Fast response (m·s)½
No In-RackEliminates rack sprinklers

How ESFR Suppression Differs from Conventional Control

1

Fast Activation

The 3mm fast-response glass bulb (RTI ≤50) shatters very early in fire development — before the thermal column reaches full strength. This is the same bulb used in Quick Response sprinklers, but here it triggers a dramatically higher flow rate.

2

High-Volume Discharge

At the minimum design pressure, an ESFR-363 (K25.2) delivers over 3× the flow of a standard K5.6 sprinkler. This volume of water is needed to penetrate the intense thermal updraft above a high-challenge rack fire and reach burning commodities at lower levels.

3

Suppression, Not Just Control

Conventional sprinklers aim to prevent fire spread. ESFR is designed to achieve fire suppression — reducing heat release rate below the threshold needed for sustained burning, even with high-piled or rack-stored commodities up to 12 m high.

The key economic case for ESFR: A conventional wet-pipe sprinkler system in a high-bay storage facility typically requires both ceiling sprinklers and in-rack sprinklers at every two or three storage levels. ESFR eliminates the in-rack requirement entirely in eligible configurations — reducing material cost, installation labour, and ongoing maintenance. For a 10,000 m² distribution centre at 12 m clear height, eliminating in-rack sprinklers can save hundreds of thousands of dollars in installed cost.

Choosing the Right K-Factor: K14.2, K17.0, or K25.2

The K-factor determines how much water an ESFR head delivers at a given pressure. Higher K-factors are used at greater ceiling heights and greater storage heights, where more water volume is needed to overcome the stronger thermal column above a larger fire. The selection is governed by the specific ceiling height, storage height, and commodity class for the project — and must follow NFPA 13 Table 20.X or GB 50084 ESFR tables exactly.

K14.2
International · K202 domestic
ESFR-202
Ceiling 9.0–10.5 m · Storage up to 9.0 m · Min. pressure 0.35 MPa (9 m ceiling)
R:3/4 Thread
K17.0
International · K242 domestic
ESFR-242
Ceiling 9.0–12.0 m · Storage up to 10.5 m · Min. pressure 0.25–0.35 MPa
Most Specified · R:3/4
K25.2
International · K363 domestic
ESFR-363
Ceiling 9.0–13.5 m · Storage up to 12.0 m · Min. pressure 0.10–0.35 MPa
High-Bay / Heavy Storage · R:1
⚠ ESFR selection requires qualified engineering: The correct K-factor, installation orientation (upright vs pendent), spacing, and design pressure must be determined by a licensed fire protection engineer or designer using the current edition of NFPA 13 or GB 50084. Ceiling height, storage height, commodity class, aisle width, rack configuration, and obstruction layout all affect which ESFR model and pressure are required. Do not substitute ESFR models between K-factor series without re-engineering the hydraulic design.

ESFR Sprinkler Models — ESFR-202 / ESFR-242 / ESFR-363

All ESFR models use a fast-response glass bulb (RTI ≤50). Available in upright (U) and pendent (P) orientations. Activation temperatures: 68°C, 74°C, 82°C, 100°C depending on series and orientation.

ESFR-202 68°C U upright ESFR sprinkler K14.2 CA-FIRE

ESFR-202 68°C / 74°C U

Upright · K14.2 · ESFR

K14.2 upright ESFR. For ceiling heights 9.0–10.5 m, storage up to 9.0 m. Mounts above branch pipe — suited to exposed-pipe systems and situations where pendent installation is not possible.

K-factor (intl.)K14.2 (K202)
Activation temps68°C / 74°C
Max ceiling10.5 m
Max storage9.0 m
ThreadR:3/4 (BSP)
ESFR-202 68°C P pendent ESFR sprinkler K14.2 CA-FIRE

ESFR-202 68°C / 74°C / 100°C P

Pendent · K14.2 · ESFR

K14.2 pendent ESFR. Hangs below branch pipe. Broader temperature range including 100°C for high-ambient areas. Ceiling 9.0–12.0 m, storage up to 10.5 m at appropriate pressure.

K-factor (intl.)K14.2 (K202)
Activation temps68°C / 74°C / 100°C
Max ceiling12.0 m
Max storage10.5 m
ThreadR:3/4 (BSP)
ESFR-242 74°C U upright ESFR sprinkler K17.0 CA-FIRE

ESFR-242 74°C U

Upright · K17.0 · Most Specified

The most widely specified ESFR model. K17.0 upright for ceiling heights 9.0–10.5 m, storage up to 9.0 m. Achieves suppression at lower minimum pressures than K14.2 for the same ceiling height.

K-factor (intl.)K17.0 (K242)
Activation temps74°C
Max ceiling10.5 m
Max storage9.0 m
ThreadR:3/4 (BSP)
ESFR-242 74°C P pendent ESFR sprinkler K17.0 CA-FIRE

ESFR-242 74°C P

Pendent · K17.0 · Most Specified

K17.0 pendent ESFR. For ceiling heights up to 12.0 m, storage up to 10.5 m. The pendent orientation is preferred in concrete deck construction where drainage from upright heads is a concern.

K-factor (intl.)K17.0 (K242)
Activation temps74°C
Max ceiling12.0 m
Max storage10.5 m
ThreadR:3/4 (BSP)
ESFR-363 74°C U upright ESFR sprinkler K25.2 CA-FIRE

ESFR-363 74°C / 82°C / 100°C U

Upright · K25.2 · High-Bay

Highest K-factor ESFR. Upright installation for exposed-pipe high-bay facilities. Ceiling up to 13.5 m, storage up to 12.0 m. Lowest minimum design pressure of any ESFR series at equivalent heights.

K-factor (intl.)K25.2 (K363)
Activation temps74°C / 82°C / 100°C
Max ceiling13.5 m
Max storage12.0 m
ThreadR:1 (BSP)
ESFR-363 74°C P pendent ESFR sprinkler K25.2 CA-FIRE

ESFR-363 74°C / 82°C / 100°C P

Pendent · K25.2 · High-Bay

K25.2 pendent for concrete deck high-bay distribution centres. Ceiling up to 13.5 m, storage up to 12.0 m. Delivers the highest flow rate per head of any ESFR in the CA-FIRE range.

K-factor (intl.)K25.2 (K363)
Activation temps74°C / 82°C / 100°C
Max ceiling13.5 m
Max storage12.0 m
ThreadR:1 (BSP)

Complete ESFR Design Parameters Table

Select model based on maximum clear ceiling height (to underside of roof structure) and maximum storage height. Minimum working pressure must be verified by hydraulic calculation for the specific installation — values below are the NFPA 13 / GB 50084 minimum listed pressures for each configuration.

Model K-factor (intl.) Installation Max Ceiling Height Max Storage Height Min. Working Pressure Spacing Range Thread
ESFR-202 · K14.2 (K202) · 68°C / 74°C / 100°C · Fast Response
ESFR-202/68°C UK14.2Upright 9.0 m6.0 m0.35 MPa2.4–3.7 mR:3/4
ESFR-202/74°C UK14.2Upright 9.0 m6.0 m0.35 MPa2.4–3.7 mR:3/4
ESFR-202/68°C PK14.2Pendent 9.0 m6.0 m0.35 MPa2.4–3.7 mR:3/4
ESFR-202/74°C PK14.2Pendent 10.5 m9.0 m0.50 MPa2.4–3.7 mR:3/4
ESFR-202/82°C PK14.2Pendent 12.0 m10.5 m0.50 MPa2.4–3.7 mR:3/4
ESFR-202/100°C PK14.2Pendent 12.0 m10.5 m0.50 MPa2.4–3.7 mR:3/4
ESFR-242 · K17.0 (K242) · 74°C · Fast Response · Most Specified
ESFR-242/74°C U ★K17.0Upright 9.0 m6.0 m0.25 MPa2.4–3.7 mR:3/4
ESFR-242/74°C P ★K17.0Pendent 9.0 m6.0 m0.25 MPa2.4–3.7 mR:3/4
ESFR-242/74°C U (10.5 m)K17.0Upright 10.5 m9.0 m0.35 MPa2.4–3.7 mR:3/4
ESFR-242/74°C P (10.5 m)K17.0Pendent 10.5 m9.0 m0.35 MPa2.4–3.7 mR:3/4
ESFR-242/74°C P (12.0 m)K17.0Pendent 12.0 m10.5 m0.50 MPa2.4–3.7 mR:3/4
ESFR-363 · K25.2 (K363) · 74°C / 82°C / 100°C · Fast Response · High-Bay
ESFR-363/74°C UK25.2Upright 9.0 m6.0 m0.15 MPa2.4–3.0 mR:1
ESFR-363/74°C PK25.2Pendent 9.0 m6.0 m0.15 MPa2.4–3.0 mR:1
ESFR-363/82°C U (10.5 m)K25.2Upright 10.5 m9.0 m0.20 MPa2.4–3.0 mR:1
ESFR-363/82°C P (10.5 m)K25.2Pendent 10.5 m9.0 m0.20 MPa2.4–3.0 mR:1
ESFR-363/100°C U (12.0 m) ★K25.2Upright 12.0 m10.5 m0.35 MPa2.4–3.0 mR:1
ESFR-363/100°C P (12.0 m) ★K25.2Pendent 12.0 m10.5 m0.35 MPa2.4–3.0 mR:1
ESFR-363/100°C P (13.5 m)K25.2Pendent 13.5 m12.0 m0.35 MPa2.4–3.0 mR:1

★ Most commonly specified configurations. Min. pressure = minimum design pressure at the sprinkler — actual system demand depends on hydraulic calculation including pipe friction losses. All models GB 5135 CCCF certified. NFPA 13 submittals available on request.

Key System Design Requirements for ESFR

ESFR systems place significantly higher demands on the water supply and distribution system than conventional sprinkler systems. The following parameters must be verified at the design stage — they cannot be retrofitted economically after installation.

Design Basis
12 heads
NFPA 13: max 12 most hydraulically demanding ESFR heads operate simultaneously
Min. Pressure at Head
0.15–0.50 MPa
Depends on K-factor and ceiling height — see table above
Max Spacing
3.7 m × 3.7 m
K202/K242; K363 max 3.0 m × 3.0 m
Min Spacing
2.4 m
All K-factors — prevents simultaneous activation of adjacent heads
Ceiling Clearance
≥ 1.0 m
Minimum clearance between top of storage and sprinkler deflector
Obstructions
Clear ceiling
No beams or structural elements between heads — strict NFPA 13 Section 20 rules apply
Aisle Width
≥ 2.4 m
Transverse aisles must be at least 2.4 m wide for ESFR eligibility
In-Rack Sprinklers
Not required
ESFR ceiling-only approach eliminates in-rack requirement in eligible configurations

ESFR vs Conventional Ceiling + In-Rack System

Parameter Conventional Ceiling + In-Rack ESFR Ceiling-Only
Fire objective Control — limit spread, protect structure Suppression — extinguish or reduce below sustaining threshold
In-rack sprinklers required Yes — typically every 2–3 rack levels No — eliminated in qualifying configurations
K-factor at ceiling K5.6–K8.0 (standard response) K14.2–K25.2 (ESFR)
Response type Standard Response (5mm bulb) or QR Fast Response (3mm bulb · RTI ≤50)
Water demand Lower per ceiling head; high total when rack heads included High per head; lower total (12 heads only)
Installation complexity High — ceiling + rack pipe networks, multiple zones Lower — ceiling-only pipe network
Rack re-configuration flexibility Low — changing rack layout requires re-piping rack sprinklers High — rack layout can change without re-piping ceiling system
Maintenance Higher — rack sprinklers are vulnerable to forklift damage Lower — ceiling sprinklers only, no rack exposure
Max ceiling height Effectively unlimited with in-rack levels Up to 13.5 m (K25.2 models)
Eligible storage types Class I–IV, Group A plastics, all commodities Class I–IV, limited Group A plastics — verify commodity class with designer

Typical ESFR Applications

ESFR sprinklers are specified wherever high-piled or rack-stored commodities are held in facilities with ceiling heights that exceed the practical limit for standard sprinkler systems. The common thread in all ESFR applications is a high-bay building with regular rack or pallet storage and the ability to maintain clear ceiling conditions.

📦
Distribution Centres
K17.0 / K25.2 — ESFR-242 / ESFR-363

High-bay distribution and fulfilment centres with pallet or selective rack storage up to 12 m. The most common ESFR application globally.

🏗️
High-Bay Storage Facilities
K25.2 — ESFR-363

Purpose-built high-bay stores with ceiling heights 10–13.5 m. ESFR-363 eliminates the need for multi-tier in-rack sprinkler networks.

🛒
Retail Back-of-House & DCs
K14.2 / K17.0

Large-format retail warehousing and stockrooms with rack storage. ESFR enables flexible rack layouts that can be reconfigured without re-piping.

🏭
Cold Chain & Refrigerated Stores
K17.0 / K25.2 · 74°C models

Chilled and frozen storage with racking — where ambient temperatures are low but stored commodities may present significant fire hazard.

🚚
Logistics & 3PL Hubs
K17.0 — ESFR-242

Third-party logistics hubs handling mixed commodity types with frequently changing rack layouts — where ESFR's layout flexibility is a key advantage.

🏬
Wholesale & Cash & Carry
K14.2 / K17.0

Wholesale trade stores with high-bay shelving — ceiling-only ESFR avoids rack sprinklers in areas where product accessibility is important.

Frequently Asked Questions

Can ESFR sprinklers protect any type of stored commodity?

No — ESFR systems are approved for Class I through Class IV commodities and some Group A plastics configurations under NFPA 13. They are generally not permitted for storage of aerosols, flammable liquids, certain plastics, or commodities with unusual packaging that significantly increases fire hazard beyond the tested categories.

The specific commodity class, packaging type, storage arrangement, and aisle configuration must all be verified against the NFPA 13 ESFR tables for the K-factor and ceiling height being used. A fire protection engineer must confirm eligibility before specifying ESFR for any project.

What is the difference between upright (U) and pendent (P) ESFR models — which should I specify?

Both achieve the same suppression performance. The choice between upright and pendent depends on the building structure and the piping system design:

Upright (U) models mount above the branch pipe with the deflector facing upward. They are preferred in facilities with exposed steel structure where the pipe is run along the underside of roof purlins. Upright installation also aids drainage — water drains from the pipe back through the sprinkler body when the system drains, which matters for dry-pipe or pre-action systems.

Pendent (P) models hang below the branch pipe. They are commonly used in facilities with flat concrete decks or suspended ceilings where the pipe is run above. Some ESFR pendent models are available at higher temperature ratings (e.g. 100°C) not available in the upright format, providing greater flexibility at higher storage heights.

Why does the minimum pressure change with ceiling height?

The minimum listed pressure for an ESFR sprinkler is determined by full-scale fire testing at each specific ceiling height and storage configuration. At greater ceiling heights, the fire has more time to grow before the sprinkler activates, producing a more powerful thermal column above the fire. More pressure — and therefore more flow — is required to drive water through that stronger updraft and reach the burning commodity at storage level.

This is why a K25.2 (ESFR-363) at 9 m ceiling height requires only 0.15 MPa, while the same K25.2 head at 12 m ceiling height requires 0.35 MPa. The suppression mechanism requires the water to physically penetrate the plume — higher plume energy requires higher discharge momentum.

Can ESFR sprinklers be used with a dry-pipe or pre-action system?

ESFR sprinklers are strongly preferred with wet-pipe systems. Dry-pipe and pre-action systems introduce a delay between sprinkler activation and water delivery — during this delay, the fire continues to grow and the thermal column strengthens. NFPA 13 permits ESFR with dry-pipe systems only under restricted conditions and with tighter spacing requirements, because the delayed water delivery means the system must deliver even more water to achieve suppression once flow begins.

For cold-storage applications where freezing makes wet pipe impractical, a glycol-charged wet-pipe system or an anti-freeze loop is typically preferred over dry-pipe with ESFR. Consult your system designer for the appropriate solution for your specific environment.

Our facility ceiling is 8 m. Can we use ESFR?

The minimum ceiling height for ESFR eligibility under NFPA 13 and GB 50084 is 9.0 m clear height (to the underside of roof structure). Below 9 m, the distance between the sprinkler deflector and the top of the storage is insufficient for the ESFR spray pattern to fully develop before it reaches the commodity. At 8 m ceiling height, a conventional standard response or quick response ceiling system — potentially with in-rack sprinklers if storage height is substantial — is the appropriate solution. See our Standard Response Sprinkler page for options.

How do I convert between K202 / K242 / K363 (domestic) and K14.2 / K17.0 / K25.2 (international)?

The conversion factor is ÷ 14.28: the domestic K-factor number (in L/min / (MPa)½ units) divided by 14.28 gives the international K-factor (in gpm / (psi)½ or L/min / (bar)½ depending on regional convention).

  • K202 ÷ 14.28 = K14.2
  • K242 ÷ 14.28 = K17.0
  • K363 ÷ 14.28 = K25.2

When requesting NFPA 13 submittals or export documentation, CA-FIRE uses international K-factor designations. For GB 50084 submittals, domestic K-factor numbers are used.

Related Products

Request a Quote — CA-FIRE ESFR Sprinklers

ESFR-202 (K14.2) · ESFR-242 (K17.0) · ESFR-363 (K25.2) · Upright & Pendent

GB 5135 CCCF Certified · NFPA 13 documentation available · Technical support included · 24 hr quote

sales@ca-fire.com  ·  WhatsApp +86 18150362095

Send Inquiry →
Scroll to Top